| 2004-09-21 00:00:00 | ************ UNSAT ***************** |
| | |
| | 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | PLEASE ALSO SEE 210.52C1-5 FOR REQUIRED |
| | RECEPTS/SPACING. |
| | |
| | 2) NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | PLEASE SEE UNIT HAS BEEN CONVERTED FROM |
| | COMMERICAL TO RESIDENTIAL USE. |
| | RECEPT SPACING TO MEET ABOVE. |
| | |
| | 3 )NOTE: PLEASE SEE MISSING REQ'D EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210.70 AND LS-101 5-8 |
| | PLEASE SEE EXITING INTO HALLWAY FROM |
| | UNIT. APPEARS TO TURN ON A LT OUTSIDE |
| | BUT NOT IN HALL. |
| | |
| | 4)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 210.12 2002 NEC. |
| | |
| | 5)NOTE: PLEASE SEE MAIN ELECTRICAL ROOM |
| | IS BEING SHOWN ON FIRST FLOOR AND ALSO |
| | INSIDE RESIDENTIAL UNIT. |
| | THIS INDICATES ELECTRICAL IN THIS ROOM |
| | FEEDING UPSTAIRS RESIDENTIAL UNIT.\ |
| | THIS IS NOT PERMITTED. |
| | UPSTAIRS RESIDENT MUST HAVE ACCESS TO |
| | MEANS OF DISCONNECT FOR HIS/HER OWN |
| | RESIDENTIAL UNIT W/OUT ENTERING THE |
| | RESIDENCE OF ANOTHER. |
| | 230.70,225.31,225.32,2255.35 ETC. |
| | THIS ROOM WOULD BE REQUIRED TO BUILT |
| | SEPARATE FROM EACH UNIT WITH A MIN OF |
| | 1-HOUR RATING. |
| | PLEASE ALSO SEE 230.72 FOR GROUPING OF |
| | MAINS TO BLDG. |
| | |
| | 6)NOTE: PLEASE SEE EXISTING GARAGE IS |
| | REQUIRED TO SHOW EITHER NEW ELECTRICAL |
| | OR EXISITNG ELECTRICAL TO MEET 2002 NEC. |
| | PLEASE ALSO SEE FBC CHAPTER 34 3401.7.2- |
| | .6. |
| | PLEASE ALSO SEE DUE TO CHANGE IN |
| | OCCUPANCY, MUST ALSO BE BROUGHT UP TO |
| | CODE. |
| | |
| | 7)NOTE: PLEASE SEE 210.52D WHICH REQUIRE |
| | -S A GFI RECEPT A MAX OF 3' FROM SINK/ |
| | LAVS IN BATH RMS. |
| | |
| | 8)NOTE: PLEASE SEE WALK-IN CLOSET WHICH |
| | SHOWS AHU AND WATER HEATER. PLEASE SEE |
| | 110.26 FOR MIN CLEARENCE FOR DISC MEANS. |
| | PLEASE ALSO SEE 422.17 FOR WATER HEATER. |
| | |
| | 9 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 10)NOTE: PLEASE VERIFY 7.2KW SHOWN FOR |
| | AHU'S FOR FIRST FLR LOAD CALCUALTIONS.?? |
| | PLEASE SEE ALL AHU LOADS ON PANEL SCHED- |
| | -ULES. THESE DO NOT SEEM TO CORRELATE. |
| | PLEASE ALSO SEE 220.31B FOR FIGURING |
| | HEAT LOAD OF AHU'S. |
| | |
| | 11)NOTE: PLEASE SEE TWO "EXISTING" DISC |
| | "C"?? |
| | PLEASE CORRELATE AND LABEL ACCORD. |
| | 230.2E |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWER- |
| | (S) WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT NEW SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |