| 2004-07-30 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | |
| | 1) SHT A-4.0 SUBMIT CALCULATIONS FOR |
| | ROOF SCUPPERS. SHOW SQUARE FOOTAGE FOR |
| | EACH AREA OF ROOF AND SHOW 1/2 AREA OF |
| | VERTICAL WALLS INCLUDING PARAPETS AS ITS |
| | ADDED TO ROOF AREA. INDICATE TOTAL SF |
| | FOR EACH DRAIN. LOWER ROOF CALCULATIONS |
| | ALSO. SECTIONS 1106 & 1107 AND ALL SUB- |
| | SECTIONS. - SCUPPER DRAIN SHALL BE SIZED |
| | LARGE ENOUGH TO FOR PRIMARY AND SECOND- |
| | ARY DRAINS. |
| | 2) SHT A-7.0 COFFEE AREA SINK, A CLEAR |
| | FLOOR SPACE SHALL BE PROVIDED IN FRONT |
| | OF THE SINK TO ALLOW FORWARD APPROACH |
| | MAXIMUM OF 19" UNDER THE SINK. - ALSO |
| | PER THE BLDG OFFICIAL CABINET DOORS AT |
| | CLEAR SPACE CREATE A HARDSHIP AND SHALL |
| | NOT BE INSTALLED. SECTION 11-4.24.5 - |
| | ALSO SHOW KNEE CLEARANCE SECTION 4.24.3. |
| | 3) SECTION 11-4.24.4 SINK DEPTH SHALL BE |
| | A MAXIMUM OF 6-1/2" DEEP. SINK REFERENC- |
| | ED ON SHEET M-1 FIXTURE SCHEDULE (3), |
| | SHOWS ELKAY MODEL ECC-2522. DEPTH OF |
| | THIS SINK IS 7-1/2" AS SHOWN ON ATTACHED |
| | SHEET. |
| | 4) SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH SECTION 11-4.15 AND ALL SUBSECTIONS |
| | (DRINKING FOUNTAIN) |
| | 5) 1204.2 SURROUNDING MATERIALS; |
| | THE WALLS & FLOORS OF ALL PUBLIC REST- |
| | ROOMS SHALL BE LINED WITH NONABSORBANT |
| | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| | FLOOR. - NOTE: SHT A-8.0 INDICATES LATEX |
| | PAINT. THIS IS NOT ACCEPTABLE AS A NON- |
| | ABSORBANT MATERIAL. |
| | 6) SHT M-1 PLUMBING NOTES #10, AIR CHAM- |
| | BERS ARE NOT APPROVED. DELETE REFERENCE |
| | FROM NOTES. SECTION 104.2.1 |
| | 7) SEPARATE IRRIGATION PLANS AND PERMIT |
| | ARE REQUIRED. SECTION 1-4.3.1.1 |
| | 8) SECTION 607.3.1 THERMAL EXPANSION |
| | CONTROL IS REQUIRED. |
| | |