| Plan Review Notes For Permit 04070546 |
| Permit Number |
04070546 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-02 00:00:00 | FAILED : | | | 1. CIVIL/SITE PLANS MUST BE REVIEWED AND | | | APPROVED BY THE PUBLIC UTILITIES & | | | ENGINEEING FOR ALL THE CONNECTIONS PRIOR | | | TO SUBMITTING TO THE BUILDING DEPARTMENT | | | , ATT;MANNY GONZALEZ, 494-1085. | | | 2. PLEASE SUBMIT STORM WATER CALCULATION | | | FOR OUR REVIEW AND APPROVAL, IT SHOULD | | | INCLUDE PERVIOUS AND IMPERVIOUS,BUILDING | | | AREA FOR THE ENTIRE SITE. | | | 3. ANY EXISTING METERS THAT IS NOT GOING | | | TO BE USED MUST BE REMOVED AND LINE | | | MUST BE PLUGED, PER CITY REQUIREMENTS. | | | 4. WORK WITHIN PUBLIC R.O.W (45TH ST.) | | | REQUIRES A SEPARATE PERMIT FROM PB | | | COUNTY AND FROM CWPB PUBLIC UTILITIES & | | | ENGINEERING, WINDEL PALMER 494-1086. | | | 5. PLEASE CLARIFY WITH PUBLIC UTILITIES | | | AND ENGINEERING AS WHO AND HOW THE CANAL | | | BANK WILL BE MAINTAINED. CONSTRUCTION OF | | | CONCRETE WALL, AS PROPOSED. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|