2004-07-27 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 2) PIPING SCHEMATIC DOES NOT REFLECT THE
 POOL LAYOUT. SCHEMATIC SHOWS A TWO PUMP
 SYSTEM WITH AUX. POOL JETS. NOT SHOWN ON
 THE POOL LAYOUT OR SHOWN ON THE POOL
 DATA & EQUIPMENT SCHEDULE. PLEASE CORRE-
 LATE SCHEMATIC WITH POOL LAYOUT/EQUIP.
 SCHEDULE. SECTION 104.2.1
 3) GENERAL NOTES: TESTS, INDICATES AIR
 TEST, THIS IS NOT APPROVED. PLEASE DELE-
 TE FROM NOTES. SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]