| 2004-10-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | PIPE SIZING FOR EXISTING AND NEW PIPE | | | ARE NOT SUFFICIENT FOR THE ADDED LOAD OF | | | THE POOL HEATER @ 100'. EIGHER A 2 LB | | | SYSTEM WITH A REGULATOR OR LARGER PIPE | | | IS REQUIRED. TABLE 402(2). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|