Plan Review Notes
Plan Review Notes For Permit 04070519
Permit Number 04070519
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-24 00:00:00*** PROVISO/ REVISION ******
  
 1)NOTE:
 PLEASE SEE CONDUIT FOR TYPICAL UNITS
 AS 1 1/2" MUST BE SIZED PER NEC TABLES.
 IF PVC THIS CONDUIT IS TOO SMALL.
  
 2)NOTE:
 PLEASE ALSO SEE PREVIOUS NOTES FOR
 A MIN OF ONE LT FIXTURE REQUIRED FOR
 LS 101 5-8. PLANS STILL SHOW J-BOX AND
 NO LT FIXTURE.
  
 PLANS ARE TO BE REVISED AND SUBMITTED
 FOR REVIEW BEFORE ROUGH ELECTRICAL
 INSPECTION IS CALLED. IN.
  
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717