2004-07-29 00:00:00DENIED
 REFRERENCE: FBC-2001 PLUMBING
  
 1) SHT 1 DRINKING FOUNTAINS ARE REQUIRED
 FOR EACH SPACE. TABLE 403.1 - ALSO SEE
 SECTION 410.1.
 2) SHT 2 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS