| Plan Review Notes For Permit 04070519 |
| Permit Number |
04070519 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-29 00:00:00 | DENIED | | | REFRERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT 1 DRINKING FOUNTAINS ARE REQUIRED | | | FOR EACH SPACE. TABLE 403.1 - ALSO SEE | | | SECTION 410.1. | | | 2) SHT 2 WATER RISER DIAGRAM, WATER | | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | | THE FIXTURE IN AN "EFFECTIVE RANGE" NOT | | | IN THE CEILING AS SHOWN. PDI-WH 201 AND | | | MANUF. INSTALLATION INSTRUCTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|