Plan Review Notes
Plan Review Notes For Permit 04070519
Permit Number 04070519
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-19 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE CORRELATE CIRCUIT #'S
 AHOWN ON PLANS WITH PANEL SCHEDULE.
 PLEASE SEE 700.12E. EM LT SHOWN ON
 SHOW WINDOW CIRCUITS.
 PLEASE SHOW A MIN OF ONE COMPLETE TYP
 UNIT.
  
 2)NOTE: PLEASE SEE FEEDERS TO 150A
 PANELS. THESE DO NOT SHOW A NEUTRAL?
 PLEASE ALSO CHECK CONDUIT TYOE AND SIZE.
  
 3)NOTE: PLEASE SEE 210.62 FOR REQ'D
 SHOW WINDOW RECEPTS. PANEL SCHEDULE
 INDICATES CIRCUITS BUT PLAN DOES NOT
 SHOW RECEPTS??
  
 4)NOTE: PLEASE SEE LS 101 5-8 WHICH
 REQUIRES A MIN EGRESS LIGHTING IN BLDG.
 PLANS SHOW OUTLETS AS BEING J-BOX ONLY
 AND NO FIXTURE INDICATED. A MIN OF ONE
 LT SHALL BE REQUIRED.
  
 5 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 TYP NOTE"
  
 PLEASE VERIFY NOTE IN THE MIDDLE OF PLAN
 -S CALL FOR EXISTING ELEC TO REMAIN UON?
 PLEASE CLARIFY, PLANS ARE SHOWING ALL
 AS NEW AT THIS TIME??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
 WATER/ ETC. SIZE ALL PER 250.66