| 2004-07-19 00:00:00 | ************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE CORRELATE CIRCUIT #'S |
| | AHOWN ON PLANS WITH PANEL SCHEDULE. |
| | PLEASE SEE 700.12E. EM LT SHOWN ON |
| | SHOW WINDOW CIRCUITS. |
| | PLEASE SHOW A MIN OF ONE COMPLETE TYP |
| | UNIT. |
| | |
| | 2)NOTE: PLEASE SEE FEEDERS TO 150A |
| | PANELS. THESE DO NOT SHOW A NEUTRAL? |
| | PLEASE ALSO CHECK CONDUIT TYOE AND SIZE. |
| | |
| | 3)NOTE: PLEASE SEE 210.62 FOR REQ'D |
| | SHOW WINDOW RECEPTS. PANEL SCHEDULE |
| | INDICATES CIRCUITS BUT PLAN DOES NOT |
| | SHOW RECEPTS?? |
| | |
| | 4)NOTE: PLEASE SEE LS 101 5-8 WHICH |
| | REQUIRES A MIN EGRESS LIGHTING IN BLDG. |
| | PLANS SHOW OUTLETS AS BEING J-BOX ONLY |
| | AND NO FIXTURE INDICATED. A MIN OF ONE |
| | LT SHALL BE REQUIRED. |
| | |
| | 5 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | TYP NOTE" |
| | |
| | PLEASE VERIFY NOTE IN THE MIDDLE OF PLAN |
| | -S CALL FOR EXISTING ELEC TO REMAIN UON? |
| | PLEASE CLARIFY, PLANS ARE SHOWING ALL |
| | AS NEW AT THIS TIME?? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | WATER/ ETC. SIZE ALL PER 250.66 |