Plan Review Notes
Plan Review Notes For Permit 04070518
Permit Number 04070518
Review Stop P
Sequence Number 2
Notes
Date Text
2004-11-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
 3) SHT P-2.01 DOMESTIC WATER RESER
 DIAGRAM, WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE
 IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 NO RESPONSE NOTED.
 4) SHT A-3.01 SECTION 11-4.24.5 A
 CLEAR FLOOR SPACE AT LEAST 30"X48"
 COMPLYING WITH 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO
 ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE
 ROUTE AND SHALL EXTEND A MAXIMUM OF
 19" UNDERNEATH THE SINK. (SEE FIG.32)
 THIS IS FOR THE EMPLOYEE ROOM SINK
 NOT THE LAVS. THE SPACE UNDER THE
 SINK SHALL NOT HAVE DOORS AS THEY
 ARE A HINDERENCE PER BLDG OFFICIAL.
 5) SHOW KNEE CLEARANCE 11-4.24.3,
 EXPOSED PIPES AND SURFACES 11-4.24.6,
 *****NEW COMMENT*****
 1B) SEE ATTACHED SHEET CONCERNING
 FS 553.80(2)(B)
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]