| | BUILDING PLAN REVIEW |
| | PERMIT: 04070518 |
| | ADD: 2471 OKEECHOBEE BLVD |
| | CONT: G. T. MCDONALD ENT |
| | TEL: (954)650-0022 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) REMOVE THE OLD SHEETS (VOID) FROM THE |
| | PLANS AND SUBMIT ONE SET OLD SHEETS |
| | PLUS |
| | THE 2 SETS OF CORRECTED PLANS FOR |
| | RESUBMITAL. |
| | |
| | 3) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | QUESTIONS ABOUT THE OVERHEAD TRELLIS |
| | WORK ARE: |
| | A) PLANS INDICATE THE USE OF AIRCRAFT |
| | CABLES TO HANG TRELLIS WORK FROM THE |
| | BAR JOIST ABOVE.NO INFORMATION AS TO |
| | THE |
| | CABLE WIDTH, HOW MANY CLAMPS ARE TO BE |
| | USED. ALSO PLANS DO NOT INDICATE HOW |
| | OFTEN THE HEADER IS TO BE HUNG NOR HOW |
| | LONG THE TIMBERS SHOULD BE. |
| | B) PLANS DO NOT SPECIFY THE SIZE OF THE |
| | |
| | EYEBOLTS TO BE USED? |
| | C) ENGINEER TO EVALUATE THE ADDITIONAL |
| | |
| | LOADING OF THE TRELLIS WEIGHT, ALSO TO |
| | INDICATE WHERE THE ADDITIONAL WEIGHT IS |
| | TO BE APPLIED TO THE BARJOIST, TOP OR |
| | BOTTOM CHORD. |
| | D)DETAIL# 1 INDICATE STEEL BUCKETS |
| | ATTACHED TO THE BLOCK WALL BUT NO |
| | ATTACHMENT NOR THICKNESS OF STEEL USED. |
| | E) DETAIL# 5 NO INFORMATION ON WELD. |
| | |
| | 4) COMMENT #9 FROM PREVIOUS REVIEW, WAS |
| | WHAT TYPE OF MATERIAL TO BE USED FOR |
| | CROWN MOLDING. RESPONCE SEE CUT SHEETS. |
| | THE FOAM TRIM CUT SHEETS DO NOT MEET THE |
| | |
| | CRITERIA SET FORTH IN 803.4. |
| | 803.4 FOAM PLASTIC TRIM SHALL NOT BE |
| | USED AS INTERIOR TRIM. SEE EXCEPTION: |
| | A) THE MINIMUM DENSITY IS 20LBS/CU FT. |
| | B) THE MAXIMUM THICKNESS OF THE TRIM IS |
| | 1/2" AND THE MAXIMUM WIDTH IS 4".C) |
| | THE TRIM CONSTITUTES NO MORE THAN |
| | 10% OF THE WALL OR CEILING. |
| | D) THE FLAMESPREAD RATING DOES NOT |
| | EXCEED 75 WHEN TESTED PER ASTM E 84. |
| | THE SMOKE DEVELOPMENT RATING IS |
| | NOT LIMITED. |
| | |
| | 5) SHEET A-402 DETAIL# 1 INDICATES THE |
| | USE OF CULTURED STONE FACING, PROVIDE |
| | ADDITIONAL INFORMATION AS WHAT THIS |
| | MATERIAL WILL BE. ALSO SHEET A-401 THE |
| | INTERIOR ELEVATION# 6 HAS A NEW AREA |
| | HIGHLIGHTED REVISION# 1, WHAT WILL THIS |
| | MATERIAL ALSO BE MADE OF? |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |