Text |
| 2004-07-29 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHTS D-2.01 & P-1.01 DEMO NOTES #'S 4 |
| | AND 10, AND ITEM #2, SECTION 704.5 IN |
| | THE INSTALLATION OR REMOVAL OF ANY PART |
| | OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE |
| | PROHIBITED. |
| | 2) SHTS P-1.01 & P-2.01 UNABLE TO READ |
| | THE CERTIFICATE OF AUTHORIZATION REQUIR- |
| | ED BY FAC 61G15-23.002(2) & FS 471.025. |
| | 3) SHT P-2.01 DOMESTIC WATER RISER DIAG- |
| | RAM, WATER HAMMER ARRESTORS SHALL BE LO- |
| | CATED NEAR THE FIXTURE IN AN "EFFECTIVE |
| | RANGE" NOT IN THE CEILING AS SHOWN. PDI- |
| | WH 201 AND MANUF. INSTALLATION INSTRUCT- |
| | IONS. |
| | 4) SHT A-301, SECTION 11-4.24.5 A CLEAR |
| | FLOOR SPACE AT LEAST 30"X48" COMPLYING |
| | WITH 11-4.2.4 SHALL BE PROVIDED IN FRONT |
| | OF A SINK TO ALLOW FORWARD APPROACH. THE |
| | CLEAR FLOOR SPACE SHALL BE ON AN ACCESS- |
| | IBLE ROUTE AND SHALL EXTEND A MAXIMUM OF |
| | 19" UNDERNEATH THE SINK. (SEE FIG. 32). |
| | 5) SHOW KNEE CLEARANCE 11-4.24.3, EXPOS- |
| | ED PIPES AND SURFACES 11-4.24.6, AND |
| | THE SINK SPECIFIED ON PLANS DOES NOT |
| | MEET THE DEPTH REQUIREMENTS OF SECTION |
| | 11-4.24.4 OF 6-1/2" (SEE ATTACHED SHEET) |
| | |