Plan Review Notes
Plan Review Notes For Permit 04070518
Permit Number 04070518
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHTS D-2.01 & P-1.01 DEMO NOTES #'S 4
 AND 10, AND ITEM #2, SECTION 704.5 IN
 THE INSTALLATION OR REMOVAL OF ANY PART
 OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED.
 2) SHTS P-1.01 & P-2.01 UNABLE TO READ
 THE CERTIFICATE OF AUTHORIZATION REQUIR-
 ED BY FAC 61G15-23.002(2) & FS 471.025.
 3) SHT P-2.01 DOMESTIC WATER RISER DIAG-
 RAM, WATER HAMMER ARRESTORS SHALL BE LO-
 CATED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-
 WH 201 AND MANUF. INSTALLATION INSTRUCT-
 IONS.
 4) SHT A-301, SECTION 11-4.24.5 A CLEAR
 FLOOR SPACE AT LEAST 30"X48" COMPLYING
 WITH 11-4.2.4 SHALL BE PROVIDED IN FRONT
 OF A SINK TO ALLOW FORWARD APPROACH. THE
 CLEAR FLOOR SPACE SHALL BE ON AN ACCESS-
 IBLE ROUTE AND SHALL EXTEND A MAXIMUM OF
 19" UNDERNEATH THE SINK. (SEE FIG. 32).
 5) SHOW KNEE CLEARANCE 11-4.24.3, EXPOS-
 ED PIPES AND SURFACES 11-4.24.6, AND
 THE SINK SPECIFIED ON PLANS DOES NOT
 MEET THE DEPTH REQUIREMENTS OF SECTION
 11-4.24.4 OF 6-1/2" (SEE ATTACHED SHEET)
  
 REVIEW BY KEN STEVENS