Plan Review Notes
Plan Review Notes For Permit 04070518
Permit Number 04070518
Review Stop M
Sequence Number 1
Notes
Date Text
2004-07-22 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 2.PLEASE NOTE, SHOULD RETURN AIR BE
 A PLENUM ABOVE THE CEILING, NO
 COMBUSTIBLES ALLOWED IN THE THE RETURN
 AIR PLENUM PER 2001 FBC(M) 602.2.1.
  
 3.PLANS ARE TO BE SIGNED NOT INITIALED
 BY THE ENGINEER IN ACCORDANCE WITH FS
 471.025 AND FAC 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.