Plan Review Notes
Plan Review Notes For Permit 04070518
Permit Number 04070518
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-21 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SEE CERT OF AUTH # ON
 TITLE BLOCK IS NOT VISABLE.
 FS 471.023,FAC 61G15-23.002
  
 2)NOTE: PLEASE PROVIDE LOAD CALCULATION
 FOR EXISTING DP2.
  
 3)NOTE: PLEASE SEE 220.12B FOR LOADS
 TO BE INDICATED FOR TRK LTING.
  
 4)NOTE: PLEASE VERIFY IF NEW OR EXISTING
 SHOW WINDOW RECEPTS ARE PRESENT. 210.62
 SOME RECEPTS ARE SHOWN BUT NOT CLEAR FOR
 WHAT.?
  
 5)NOTE: PLEASE VERIFY NEW OR EXSIT SIGN
 CIRCUIT PER 600.5
  
 PLEASE SEE A-SHEETS CONTAIN A "STAMP"
 FOR REQUIRED ORIGINAL SIGNATURE.
 FS 481.221
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]