| 2004-07-26 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04070518 |
| | ADD: 2471 OKEECHOBEE BLVD |
| | CONT: G. T. MC DONALD ENT. |
| | TEL: (954)650-0022 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | THIS MEANS ORIGINAL SIGNATURE!!!!!!!!!!! |
| | |
| | 3)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | PLANS INDICATE WHAT LOOKS LIKE (3) |
| | FIREPLACES, OWNER SUPPLIED, PROVIDE |
| | INFORMATION, TYPE OF MATERIALS, ETC. |
| | |
| | 4) SHEET A-2.01 STOREFRONT DOORS, EXIST- |
| | ING NOTE(SF) WHAT TYPE OF DOOR HARDWARE |
| | IS ON EXISTING DOORS? |
| | |
| | 5) SHEET CV-1 BUILDING CODE ANALYSIS: |
| | TYPE IV CONSTRUCTED, UNPROTECTED AND |
| | SPRINKLERED. TABLE 500 FOR MEWCANTILE |
| | OCCUPANCY ONLY ALLOWS 27,000 SQ FT. |
| | BUILDING WOULD HAVE TO BE 1-HR PROTECTED |
| | FOR THIS AREA INCREASE TO 30,877. |
| | |
| | 6) SHEET A3.01 INDICATES THE USE OF A |
| | WOOD TRELLIS SYSTEM WITH DETAILS ON |
| | PAGE A-4.02 DETAILS 1 & 2. I BELIEVE |
| | THERE IS A DISCREPANCY BETWEEN DETAILS. |
| | DETAIL#1 WOULD INDICATE THE TREATMENT |
| | WITH THE NEW OWNER SUPPLIED COLUMNS. |
| | DETAIL#2 WOULD BE CORRECT, IF THERE IS A |
| | COLUMN IN THIS POSITION? THE PLAN 3/A201 |
| | DOES NOT PROVIDE SUPPORT AT EACH CON- |
| | NECTION. |
| | |
| | 7) PLANS DO NOT PROVIDE CONNECTION FOR |
| | 4"X12" TUBE STEEL AT EXTERIOR WALL. |
| | |
| | 8) OWNER SUPPLIED COLUMNS PROVIDE INFOR- |
| | MATION? TYPE OF MATERIAL? SEE 803.4. |
| | |
| | 9) PROVIDE INFORMATION ALSO ON THE TYPE |
| | OF MATERIAL TO BE USESD FOR THE CROWN |
| | MOLDING? SEE 803.4. |
| | |
| | 10) PROVIDE THE ALLOWABLE LOADS FOR |
| | 4"X12" TUBE STEEL FOR 32"-0" CLEAR SPAN? |
| | |
| | 11)TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |