| 2004-07-16 00:00:00 | *********** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE 210.52C3,5 FOR MISS- |
| | -ING RECEPT ON KITCHEN PENINSULAR. |
| | |
| | 2)NOTE: PLEASE SEE WASHER SHOWN AS 2-P |
| | BRKR? |
| | |
| | 3)NOTE: PLEASE SEE LOAD CALCUALTIONS |
| | FOR PANEL "A". IT APPEAR TO SHOW 20KW |
| | FOR A/C LOAD?? |
| | |
| | 4)NOTE: PLEASE SEE LOAD FOR FRIG IS |
| | SHOWN AT 15.0KW. (MISPRINT). |
| | |
| | 5)NOTE: PLEASE SEE PLANS INDICATE A GFI |
| | FOR JACUZZI/WHIRLPOOL TUB, BUT THIS IS |
| | NOT SHOWN ON PANEL SCHEDULE OR LOAD |
| | CALCULATIONS. |
| | |
| | 6 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | LOAD CAN ONLY BE INCLUDED IF RECESSED |
| | LTS ARE PART OF MIN GEN LT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | PLEASE SEE ONE SET OF PLANS HAVE ITEMS |
| | REDLINED. PLEASE ALSO SEE 210.8,210.52 |
| | NOTED ON PLANS. |
| | PLEASE NOTE: STUDIO WILL BE REQUIRED TO |
| | HAVE ARC FAULT PROTECTION AS IT IS |
| | CONSIDERED TO BE AN ADAPTABLE FOR |
| | SLEEPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |