| Plan Review Notes For Permit 04070420 |
| Permit Number |
04070420 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-09-10 00:00:00 | ***** UNSAT ****** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS | | | REVIEW. | | | | | | PLEASE CORRELATE ALL RISER DIAGRMA | | | EQUIPMENT. | | | PLEASE SEE MISSING PANELS,,, | | | PLEASE SEE SOME PANEL SCHEDULES DO NOT | | | INDICATE ANY FEES TO ANY SUB-PANELS?? | | | PLEASE SEE GENERATOR IS TO BE UNDER | | | SEPARATE PERMIT. | | | PLEASE INDICATE HOW PIPE FROM GENERATOR | | | DISCONNECT TO RUN TO ATS. | | | PLEASE SEE LOADS ON ONE PANEL SCHEDULE | | | "E" DOE SNOT CORRLELATE WITH SECOND | | | PANEL SCHEDULE "E". | | | PLEASE SEE RISER ON PLANS SHOWS MAIN | | | DISCONNECTS AND MLO PANELS AND OTHER | | | RISER SHOWS MCB PANELS. | | | | | | | | | PLEASE SUBMIT REVISED PLANS TO CODE | | | COMPLIANCE. | | | | | | | | | PLEASE SEE FEES OWED FOR REVISIONS PER | | | PAGE. $20, ADDITIONAL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|