2005-09-10 00:00:00***** UNSAT ******
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW.
  
 PLEASE CORRELATE ALL RISER DIAGRMA
 EQUIPMENT.
 PLEASE SEE MISSING PANELS,,,
 PLEASE SEE SOME PANEL SCHEDULES DO NOT
 INDICATE ANY FEES TO ANY SUB-PANELS??
 PLEASE SEE GENERATOR IS TO BE UNDER
 SEPARATE PERMIT.
 PLEASE INDICATE HOW PIPE FROM GENERATOR
 DISCONNECT TO RUN TO ATS.
 PLEASE SEE LOADS ON ONE PANEL SCHEDULE
 "E" DOE SNOT CORRLELATE WITH SECOND
 PANEL SCHEDULE "E".
 PLEASE SEE RISER ON PLANS SHOWS MAIN
 DISCONNECTS AND MLO PANELS AND OTHER
 RISER SHOWS MCB PANELS.
  
  
 PLEASE SUBMIT REVISED PLANS TO CODE
 COMPLIANCE.
  
  
 PLEASE SEE FEES OWED FOR REVISIONS PER
 PAGE. $20, ADDITIONAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  