| 2005-08-18 00:00:00 | *********** UNSAT *************** |
| | |
| | ** PLEASE BE SURE ALL REV'S ARE ON ONE |
| | PAGE FOR ONE PAGE REVISION FEE.**** |
| | |
| | |
| | 1)NOTE: PLEASE SEE SIGNED AND SEALED |
| | PLANS BY AN ARCHITECT MAY NOT HAVE HAND |
| | DRAWN CHANGE SON PLANS ALONG WITH WHITE |
| | OUT. PLEASE SEE NUMEROUS LOCATIONS |
| | "HIGHLIGHTED" ON PLANS. |
| | |
| | 2)NOTE: PLEASE SEE RISER DIAGRMA SHOWS A |
| | NEW GENERATOR, HOWEVER PERMIT FOR NEW |
| | GEN HAS NOT BEEN ISSUED AS OF THIS |
| | REVIEW DATE. |
| | NO REVISIONS TO BASE HOUSE PLANS FOR |
| | RISER / GEN CAN BE PASSED UNTIL GEN IS |
| | ISSUED. |
| | PLEASE CLARIFY THE FOLLOWING: |
| | SEE NO PANEL "E" SHOWN ON RISER? |
| | SEE THREE CIRCUITS SHOWN FOR MASTER |
| | BATHRM LTS? TWO ON EM PANEL AND ONE ON |
| | PANEL "A"? IS ONE OF THESE ON EM PANEL |
| | TO BE MAST BATH GFI? |
| | |
| | 3)NOTE: PLEASE SEE RECEPTS ADDED AND |
| | SHOWN AT "WET BAR" AS TO BE GFI PER |
| | 210.8A7 |
| | |
| | 4)NOTE: PLEASE SEE RISER DIAGRAM NOW |
| | SHOWS "EQUIPMENT GROUNDING" CONDUCTORS |
| | FROM METER TO MAINS. (FIRST MEANS OF |
| | DISCONNECT) |
| | PLEASE SEE 250.6,250.24, EQP GRNDS ARE |
| | ONLY INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 5)NOTE: PLEASE SEE MAIN FOR GEN FEED IS |
| | NOT GROUPED WITH MAINS PER 225.34. |
| | PLEASE SEE GOUPING OF MAINS IS REQUIRED |
| | OR IN "CLOSE PROXIMITY" , NOT ON THE |
| | OTHER SIDE OF HOUSE. |
| | PLEASE ALSO SEE PLANS INDICATE A MAIN |
| | NEXT TO METER OUTSIDE, PLEASE CORRELATE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |