| Plan Review Notes For Permit 04070420 |
| Permit Number |
04070420 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-09-24 00:00:00 | *** NOTES REDLINED 2ND REVIEW ********* | | | | | | ONE FRIGSHOWN AS 3.0KW ON A 1P20A | | | CIRCUIT?? MAX 1920W | | | | | | PLEASE SEE RECPT FOR LANDSCAPE LTS AND | | | JACUZZI NOT SHOWN W/ GFI PROTECT- | | | -ION. 210.8/680 | | | | | | PLEASE SEE RECEPT MISSING ON 2' | | | OF WALL SPACE IN BEDRM 3. | | | | | | PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | | | | PLEASE REVISE PLANS AND SUBMIT WITH ANY | | | OTHER REVISIONS BEFORE ROUGH. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|