Plan Review Notes
Plan Review Notes For Permit 04070420
Permit Number 04070420
Review Stop E
Sequence Number 2
Notes
Date Text
2004-09-24 00:00:00*** NOTES REDLINED 2ND REVIEW *********
  
 ONE FRIGSHOWN AS 3.0KW ON A 1P20A
 CIRCUIT?? MAX 1920W
  
 PLEASE SEE RECPT FOR LANDSCAPE LTS AND
 JACUZZI NOT SHOWN W/ GFI PROTECT-
 -ION. 210.8/680
  
 PLEASE SEE RECEPT MISSING ON 2'
 OF WALL SPACE IN BEDRM 3.
  
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 PLEASE REVISE PLANS AND SUBMIT WITH ANY
 OTHER REVISIONS BEFORE ROUGH.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  