Plan Review Notes
Plan Review Notes For Permit 04070420
Permit Number 04070420
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-16 00:00:00********** NOTES REDLINED ********
  
 PLEASE SEE JACUZZI/WHIRLPOOL GFI SHOWN
 ON PLANS BUT NOT IN LOAD CALCUALTIONS.
  
 PLEASE SEE MISSING RECEPT PER 210.52 IN
 BEDRM #3, 2' OF WALL.
  
 PLEASE SEE FRIG SHOWN AS 3KW ON 1P20A
 CIRCUIT. MISPRINT.
  
 PLEASE SEE RECEPT SHOWN OUTSIDE FOR
 LANDSCAPE LTS NOT GFI. 210.8
 DOES NOT NEED TO BE CORRECTED AT THIS
 TIME.
 IF PLANS HAVE ANY REVISIONS, PLEASE
 CORRECT AT THAT TIME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717