| Date |
Text |
| 2004-07-15 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE SERVICE REQUIRES A DISCONNECT PER |
| | 230.70 NEC AND PROBABLY LOCATED OUTSIDE |
| | PER 230.70 WPB AMMENDMENTS. |
| | |
| | 2} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3} PLEASE LIST ALL THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 4} PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 5} ADD NEW LOADS TO THE CALCULATION FOR |
| | A TOTAL DEMAND PER 215.15. |
| | |
| | 6} SMOKE DETECTORS ARE REQUIRED PER 8-1. |
| | 4.1.6 NFPA-72. |
| | |
| | 7} PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 8} PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6',12' RULE. |
| | |
| | 9} PLEASE NOTE THAT 2(TWO) SETS OF PLANS |
| | ARE REQUIREDFOR REVIEW PER 104.2.1 FBC. |
| | |
| | PLEASE NOTE THAT THE SIGNATURE OF THE EN |
| | GINEER IS REQUIRED ON HIS/HER SEAL PER |
| | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE |
| | INITIALS ARE NOT ACCEPTABLE PER F.B.P.E. |
| | ALSO A TITLE BLOCK IS REQUIRED, SAME COD |
| | E. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |