| Date |
Text |
| 2004-07-14 00:00:00 | DENIED |
| | |
| | 1. THE NOTICE OF COMMENCEMENT SHALL BE |
| | RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSEAND A COPY SUBMITTED TO THIS |
| | OFFICE |
| | BEFORE A PERMIT CAN BE ISSUED.BLANK |
| | FORMS ARE AVAILABLE FROM THIS OFFICE. |
| | |
| | 2. BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3.WEST PALM BEACH AMMENDMENTS TO THE |
| | FBC 104.2.1SUBMIT 2 OR MORE COPIES OF |
| | SPECIFICATIONS AND DRAWINGS, DRAWN TO |
| | SCALE AND SUFFICIENT CLARITY AND DETAIL |
| | TO INDICATE THE NATURE OF THE WORK. |
| | |
| | 4.I THE EXISTING SHED BUILDING TO |
| | BE REMAINING. IT IS ON SURVEY BUT NOT |
| | THE SITE PLAN. |
| | |
| | 5.SUBMIT 2 COPIES OF PRODUCT |
| | APPROVALS FOR ROOFING, WINDOWS, IMPACT |
| | PROTECTION AND STRAPS USED. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATIONPLEASE SEE THE STATE WEBSITE |
| | AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 6. FBC 1005.4WINDOWS IN BEDROOMS DO |
| | NOT MEET MINIMUM OPENINGS FOR EMERGENCY |
| | ESCAPE RESCUE OPENINGS. |
| | |
| | 7.SUBMIT A SOILS REPORT. |
| | |
| | 8.VALUATION IS TOO LOW BASED ON |
| | SBCCI BUILDING VALUATION DATA. |
| | 856 SQ FT. X 76.96 = $65,897 ADDITIONAL |
| | PERMIT FEES OF $876.12 ARE DUE. |
| | |
| | 9.SUBMIT ENERGY CALCS. |
| | |
| | 10.ROOF SHEATHING NAILING SCHEDULE |
| | DOES NOT MEET FBC REQUIREMENTS. |
| | |
| | 11.FBC 3401.7.1.2.1 EXISTING BUILDING |
| | SHALL COMPLY WITH THIS SECTION.SHOW |
| | ON PLANS. |
| | |
| | 12.FBC 905.2.1 SMOKE DETETORS SHALL |
| | COMPLY WITH THIS SECTION, SHOW ON PLAN. |
| | |
| | 13.SHOW ON PLAN EXISTION ROOMS ON |
| | SOUTH SIDE AND SHOW LOCATION OF |
| | EXISTING WINDOWS FOR THE BEDROOMS IN |
| | THAT AREA. |
| | |
| | ANY QUESTIONS CALL ME |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |