| Plan Review Notes For Permit 04070382 |
| Permit Number |
04070382 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-02-23 00:00:00 | | | | | | | LABEL THE PANELS SHOWN, GIVE RATINGS AND | | | SCHEDULES. INDICATE THE SIZE OF THE | | | WIREWAY SHOWN. SUPPLY CALCULATIONS FOR | | | HEATERS AND SHOW HOW FED. THE | | | TRANSFORMER SHOWN MUST TERMINATE IN A | | | SINGLE OVERCURRENT PROTECTION DEVICE. | | | SEE 240.20 | | | | | | SEE COMMENTS FROM LAST REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|