| Date |
Text |
| 2004-07-15 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE COMPUTED LOAD EXCEEDS THE |
| | SERVICE SIZE. PLEASE CHECK THE EXISTING |
| | SERVICE |
| | TO VERIFY RATING.IF THE SERVICE IS TO |
| | BE INCREASED PROVIDE A RISER DIAGRAM PER |
| | 215.5. |
| | |
| | 2} THE SMALL APPLIANCE CIRCUITS MUST |
| | COMPLY WITH 220.16(A).2@1500VA EACH, |
| | MIN. |
| | |
| | 3} THE OVEN CALCULATION MUST COMPLY WITH |
| | 220.19.8000VA MIN. |
| | |
| | 4} THE PANEL LOCATED IN THE PANTRY IS IN |
| | VIOLATION OF THE CLEARANES IN ART. 110. |
| | 26. |
| | |
| | 5} PLEASE INDICATE THE LOCATION OF THE |
| | METER WITH REGARD TO THE PANELS SO THAT |
| | COMPLIANCE WITH 230.72 CAN BE |
| | DETERMINED. |
| | |
| | 6}: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8(A)(6). |
| | |
| | 7} PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6',12'. SEE REVIEWED PLANS. |
| | |
| | 8} PLEASE SEE MISSING RECEPTACLES |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52(E). |
| | |
| | 9) PLEASE SEE RECEPTACLES SERVING THE |
| | KITCHEN COUNTERSPACE TO MEET 210.52(C) |
| | SEC'S 1,2,3,4 AND 5. |
| | |
| | 10} A RECEPTACLE IS REQUIRED IN THE POWD |
| | ER ROOM PER 210.52(D). |
| | |
| | 11} THE RECEPTACLE ON THE PATIO MUST BE |
| | GFI PER 210.8(A)(3). |
| | |
| | 12} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 13} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 14}PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | ALL INFORMATION/DRAWINGS/SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPON- |
| | SIBLE FOR THE DESIGN. SECTION 104.2.1 |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |