Plan Review Notes
Plan Review Notes For Permit 04070283
Permit Number 04070283
Review Stop P
Sequence Number 2
Notes
Date Text
2004-08-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) ORIGINAL SHT A2 HAD A SANITARY RISER
 DIAGRAM SUBMITTED. NEW SHT A2 HAS A
 WATER RISER DIAGRAM THAT HAS TRAPS SHOWN
 AND THE SANITARY RISER DIAGRAM IS MISS-
 ING. SUBMIT A SANITARY RISER DIAGRAM.
 THE SERVICE SINK AND DRINKING FOUNTAIN
 SHALL DISCHARGE DOWNSTREAM OF THE TOILET
 ROOM FIXTURES PER SECTION 909.1
 CHANGE WATER RISER BY REMOVING TRAPS.
 SECTION 104.3.1.1 & SECTION 104.2.1
  
 REVIEW BY KEN STEVENS