| Plan Review Notes For Permit 04070283 |
| Permit Number |
04070283 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) INDICATE TYPE OF WORK WILL BE DONE IN | | | WORKSHOP. - MORE COMMENTS MAY FOLLOW DE- | | | PENDING ON COMMENT RESPONSE. | | | 2) INDICATE TYPE AND AMOUNT OF MATERIAL | | | TO BE STORED IN THE WAREHOUSE. - MORE | | | COMMENTS MAY FOLLOW DEPENDING ON COMMENT | | | RESPONSE. - MSDS SHEETS MAY BE REQUIRED. | | | 3) A DRINKING FOUNTAIN IS REQUIRED PER | | | TABLE 403.1. ALSO SEE SECTION 410.1. | | | 4) A SERVICE SINK IS REQUIRED PER TABLE | | | 403.1. | | | 5) GENERAL NOTES: #6, IN THE INSTALLAT- | | | ION OR REMOVAL OF ANY PART OF A DRAINAGE | | | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. | | | SECTION 704.5. - ALL DEMO'D PIPING SHALL | | | BE INSPECTED PRIOR TO COVERING. | | | 6) SUBMIT A WATER RISER DIAGRAM. SECTION | | | 104.3.1.1. | | | 7) AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE. SECTION 608.13.2. | | | 8) SUBMIT A DETAIL FOR THE ACCESSIBLE | | | TOILET ROOM SHOWING COMPLIANCE WITH SEC- | | | TIONS 11-4.16, 11-4.19, AND 11-4.22 AND | | | ALL SUBSECTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|