Plan Review Notes
Plan Review Notes For Permit 04070283
Permit Number 04070283
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) INDICATE TYPE OF WORK WILL BE DONE IN
 WORKSHOP. - MORE COMMENTS MAY FOLLOW DE-
 PENDING ON COMMENT RESPONSE.
 2) INDICATE TYPE AND AMOUNT OF MATERIAL
 TO BE STORED IN THE WAREHOUSE. - MORE
 COMMENTS MAY FOLLOW DEPENDING ON COMMENT
 RESPONSE. - MSDS SHEETS MAY BE REQUIRED.
 3) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. ALSO SEE SECTION 410.1.
 4) A SERVICE SINK IS REQUIRED PER TABLE
 403.1.
 5) GENERAL NOTES: #6, IN THE INSTALLAT-
 ION OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5. - ALL DEMO'D PIPING SHALL
 BE INSPECTED PRIOR TO COVERING.
 6) SUBMIT A WATER RISER DIAGRAM. SECTION
 104.3.1.1.
 7) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2.
 8) SUBMIT A DETAIL FOR THE ACCESSIBLE
 TOILET ROOM SHOWING COMPLIANCE WITH SEC-
 TIONS 11-4.16, 11-4.19, AND 11-4.22 AND
 ALL SUBSECTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved