| 2004-07-13 00:00:00 | *************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH A SUBMITTED |
| | PANEL SCHEDULE. PLANS APPEAR TO HAVE |
| | ITMES SHOWN AS NEW?, YET NO #'S ARE |
| | SHOWN AND COULD NOT LOCATE ANYTHING TO |
| | INDICATE AS EXISTING? |
| | PLEASE ALSO SEE 700.12E FOR EM/EXT LTS. |
| | |
| | 2)NOTE: PLEASE SEE NEW WATER FOUNTAIN |
| | SHOWN ON PLANS. PLEASE VERIFY RECEPT |
| | IF NEEDED FOR POSSIBLE PLUG IN UNIT.?? |
| | |
| | 3)NOTE: PLEASE SEE WALL PACKS ARE SHOWN |
| | ON PLANS. ARE THESE NEW? EXSIT? IF NEW |
| | PLEASE INDICATE METHOD OF CONTROL. IF |
| | PHOTOCELL, PLEASE SHOW. PC. |
| | LS101 5-8 |
| | |
| | 4)NOTE: PLEASE SEE LOAD CALCS. LIGHTING |
| | AS SHOWN INDICATE MORE LOAD THAN SHOWN |
| | AS 2W PER SQFT. PLEASE SEE 220.4B |
| | |
| | 5)NOTE: PLANS APPEAR TO SHOW A NEW |
| | OFFICE ALSO. |
| | PLEASE SHOW ANY A/C SYSTEMS, IF THERE |
| | IS GOING TO BE ANY. THIS IS ONLY A NOTE. |
| | |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS THEY MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |