| Plan Review Notes For Permit 04070258 |
| Permit Number |
04070258 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-16 00:00:00 | **********DENIED************************ | | | 1) ON SHEETS FP-2 AND FP-3 APPEARS THAT | | | THE PUMP ROOM, GENERATOR ROOM, ELECTRIC | | | ROOM, AND TRANSFORMER VAULT ARE NOT FIRE | | | SPRINKLER PROTECTED. | | | | | | 2) PLEASE BE ADVISED THAT THE FOUR | | | STANDPIPES REQUIRES 1250 GPM FIRE PUMP | | | AND SEPARATE PERMIT APPLICATION AND CUT | | | SHEETS MAYBE REQUIRED. | | | | | | NATE MCCRAY, CAPTAIN | | | 835-2910 OR 805-6722 |
|