Plan Review Notes
Plan Review Notes For Permit 04070247
Permit Number 04070247
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-12 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 WITH PANEL SCHEDULE TO CORRELATE.
 PLEASE SHOW MIN REQUIRED CIRCUITS.
 210.52, BATHS, SM APPLS ETC.
  
 2)NOTE: PLEASE SEE LOCATION OF PANEL IS
 SHOWN FACING INTO BATHRM. PANEL IS NOT
 PERMITTED IN BATH.240.24E
  
 3)NOTE: PLEASE SHOW SD'S ARE REQUIRED
 PER NFPA-72 8-1
  
  
 4 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 5)NOTE: PLEASE SEE FBC 104.2.1
 PRINTED NAME AND SIGNATURE OF PERSON
 RESPONSIBLE FOR PLANSMUST BE ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]