2005-04-01 00:00:00******** UNSAT ************
  
 PLEASE SEE NOTES BELOW, PLEASE SEE SOME
 NOTES ARE FROM "PROVISO" SETFORTH ON
 PREVIOUS REVIEW.
  
 1)NOTE: PLEASE SEE MISSING GFI RECEPTS
 ON KITCHEN ISLAND.
 210.52C1,2,5 AND 210.8A6
  
 2)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS SHOWN FROM METER
 TO 125A MAIN.
 PLEASE SEE 250.6,250.24, THIS IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF DISC.
  
 3)NOTE: PLEASE SEE WHIRLPOOL/SPA/JUCUZZI
 TUB IS SHOWN ON PANEL SCHEDULE, HOWEVER
 PLANS DO NOT INDICATE GFI RECEPT.
  
 4)NOTE: PLEASE SEE PLANS DO NOT SHOW
 MAINS/ ATS/ GENERATOR ON PLANS. PLEASE
 SHOW SERVICE EQUIPMENT.
 "GEN IS UNDER SEPARATE PERMIT
 APPLICATION.
  
 5)NOTE: PLEASE SEE DISH/DISP SHOWN WITH
 #6 AWG? PLEASE VERIFY THIS. #6 ON 20A
 BRKR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  