| Plan Review Notes For Permit 04070210 |
| Permit Number |
04070210 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-12 00:00:00 | *********** PROVISO/NOTES *********** | | | | | | 1)NOTE: PLEASE SEE 210.52 FOR MISSING | | | RECEPTS. | | | | | | 2)NOTE: PLEASE SEE 210.52C1,2,5 FOR | | | KITCHEN COUNTER RECEPTS/ISLAND. | | | | | | 3)NOTE: PLEASE SEE PLANS ONLY SHOWN ONE | | | PANEL. PLEASE SHOW BOTH PANELS ON PLANS. | | | | | | 4)NOTE: PLEASE SEE PANEL SCHEDULE SHOWS | | | JACUZZI TUB , HOWEVER PLANS DO NOT SHOW | | | REQUIRED GFI AT TUB LOCATION? | | | | | | PLEASE SUBMIT REVISED PLAN BEFORE ROUGH | | | ELECTRICAL INSPECTION. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|