2004-07-12 00:00:00******** UNSAT ********
  
 1)NOTE: PLEASE SHOW RECEPT(S) REQUIRED
 PER 210.52D/210.11C3 BATHS.
  
 2)NOTE: PLEASE SEE KIT SHOWS NEW LAYOUT,
 PLEASE INDICATE RECEPT REQUIRED PER
 210.52C1-5
 PLEASE SHOW RECEPTS TO BE GFI/GFI
 PROTECTED. 210.8,210.8A6
 NOTE MENTIONS TO ADD PLUMOLD TO UPPER
 CABINETS, YET NONE SHOWN ON PLAN.
  
 3)NOTE: PLEASE SEE FBC 104.2.1, A PRINT-
 -ED NAME IS ALSO REQUIRED NEXT TO SIGNAT
 -URE OF PERSON RESPONSIBLE FOR PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  