| 2004-07-23 00:00:00 | ********* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE SOME NOTES FROM |
| | FIRST REVIEW NEED TO BE FULLY ADDRESSED. |
| | |
| | 2)NOTE: PLEASE SEE NOTE #4 FROM FIRST |
| | REVIEW. ARC FAULT IS NOTED, HOWEVER BOTH |
| | PANEL SCHEDULES INDICATESD'S TO KIT |
| | AND BATH CIRCUITS?? |
| | |
| | 3)NOTE: PLEASE SEE CLEARENCE FOR A/C |
| | REQUIRED PER 110.26. A/C UNITS HAVE |
| | MOVED AND NOW HAVE WALLS. PLEASE SEE |
| | PLANS. |
| | |
| | 4)NOTE: PLEASE SEE NOTE #10 FIRST REVIEW |
| | PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | PLEASE SEE LOAD CALCS ON PANEL SCHEDULES |
| | DO NOT CORREALATE WITH NEW NOTES ADDED |
| | TO PLANS FOR LT LOADS. |
| | |
| | 5)NOTE: PLEASE SEE THAT WHITE OUT AND |
| | CORRECTION MAY NOT BE ADDED TO SIGNED |
| | AND SEALED PLANS. THIS COMMENT IS PER |
| | FS 481.221. |
| | PLEASE MUST BE ORIG. ANY AND ALL CHANGES |
| | TO SIGNED AND SEALED PLANS MUST HAVE |
| | EACH ITEM , SIGNED AND DATED BY THE |
| | ARCH OF RECORD. |
| | |
| | PLEASE SEE NOTES 1,2, FROM FIRST REVIEW, |
| | SUB-PANEL ARE STILL SHOWN AS MCB ALONG |
| | WITH MAINS ON OUTSIDE OF HOUSE? |
| | 150A PANEL STILL SHOWS 2/0'S,310.15 AND |
| | GROUNDING ELECTRODE CONDUCTOR IS NOW |
| | SHOWN AS 2/0?250.66 |
| | THE ABOVE IS PERMITTED BUT IF SHOWN |
| | THIS WAY ON PLANS, THEN THEY WILL BE |
| | REQUIRED TO BE INSTALLED UNLESS REVISED |
| | PLANS ARE SUBMITTED AND PAY REVISION |
| | FEES AT A LATER DATE. THIS IS ONLY A |
| | NOTE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |