Plan Review Notes
Plan Review Notes For Permit 04070082
Permit Number 04070082
Review Stop E
Sequence Number 2
Notes
Date Text
2004-07-23 00:00:00********* UNSAT **************
  
 1)NOTE: PLEASE SEE SOME NOTES FROM
 FIRST REVIEW NEED TO BE FULLY ADDRESSED.
  
 2)NOTE: PLEASE SEE NOTE #4 FROM FIRST
 REVIEW. ARC FAULT IS NOTED, HOWEVER BOTH
 PANEL SCHEDULES INDICATESD'S TO KIT
 AND BATH CIRCUITS??
  
 3)NOTE: PLEASE SEE CLEARENCE FOR A/C
 REQUIRED PER 110.26. A/C UNITS HAVE
 MOVED AND NOW HAVE WALLS. PLEASE SEE
 PLANS.
  
 4)NOTE: PLEASE SEE NOTE #10 FIRST REVIEW
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE SEE LOAD CALCS ON PANEL SCHEDULES
 DO NOT CORREALATE WITH NEW NOTES ADDED
 TO PLANS FOR LT LOADS.
  
 5)NOTE: PLEASE SEE THAT WHITE OUT AND
 CORRECTION MAY NOT BE ADDED TO SIGNED
 AND SEALED PLANS. THIS COMMENT IS PER
 FS 481.221.
 PLEASE MUST BE ORIG. ANY AND ALL CHANGES
 TO SIGNED AND SEALED PLANS MUST HAVE
 EACH ITEM , SIGNED AND DATED BY THE
 ARCH OF RECORD.
  
 PLEASE SEE NOTES 1,2, FROM FIRST REVIEW,
 SUB-PANEL ARE STILL SHOWN AS MCB ALONG
 WITH MAINS ON OUTSIDE OF HOUSE?
 150A PANEL STILL SHOWS 2/0'S,310.15 AND
 GROUNDING ELECTRODE CONDUCTOR IS NOW
 SHOWN AS 2/0?250.66
 THE ABOVE IS PERMITTED BUT IF SHOWN
 THIS WAY ON PLANS, THEN THEY WILL BE
 REQUIRED TO BE INSTALLED UNLESS REVISED
 PLANS ARE SUBMITTED AND PAY REVISION
 FEES AT A LATER DATE. THIS IS ONLY A
 NOTE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]