Plan Review Notes
Plan Review Notes For Permit 04070082
Permit Number 04070082
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-07 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE RISER AND PANEL
 -S. PANELS ARE SHOWN AS MCB AND RISER
 SHOWS MLO?
  
 2)NOTE: PLEASE SEE CONDUCTORS SHOWN FOR
 150A DISC'S AND PANELS ARE SHOWN AS
 2/0'S. THIS IS PERMITTED AND IS ONLY A
 NOTE.
  
 3)NOTE: PLEASE SEE 250.50 FOR MISSING
 FOOTER STEEL AS PART OF THE GE SYSTEM.
  
 4 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PLEASE SEE SD'S ARE NOTED AS BEING
 WIRED INTO KIT/BATH LT CIRCUITS.
  
 5)NOTE: PLEASE SEE MISSING REQUIRED
 RECEPT FOR BATH RM. TO BE W/IN 3' OF
 SINK. 210.52D/210.11C3
  
 6)NOTE: PLEASE SEE 210.52 FOR SOME
 RECEPTSMISSING.
  
 7)NOTE: PLEASE CORRELATE LOADS SHOWN
 FOR AHU'S / AND LOAD CALCULATIONS ALONG
 WITH OCP.
 SHOWS 8KW AND 5KW ON ONE .
 LOADS IN LOAD CALCS?
  
 8)NOTE: PLEASE SEE AN ELECTRICAL WATER
 HEATER IS SHOWN ON PANEL SCHEDULE AND
 LOAD CALCS, HOWEVER PLANS ARE SHOWING
 WH AS GAS??
  
 9)NOTE: PLEASE SEE 110.26 FOR MIN SPACE
 FOR A/C CU'S. #'S 1&2."REDLINE ITEM".
  
 10)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 11)NOTE: PLEASE PROVIDE RM DESIGNATION
 ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]