| 2004-07-07 00:00:00 | ************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER AND PANEL |
| | -S. PANELS ARE SHOWN AS MCB AND RISER |
| | SHOWS MLO? |
| | |
| | 2)NOTE: PLEASE SEE CONDUCTORS SHOWN FOR |
| | 150A DISC'S AND PANELS ARE SHOWN AS |
| | 2/0'S. THIS IS PERMITTED AND IS ONLY A |
| | NOTE. |
| | |
| | 3)NOTE: PLEASE SEE 250.50 FOR MISSING |
| | FOOTER STEEL AS PART OF THE GE SYSTEM. |
| | |
| | 4 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | PLEASE SEE SD'S ARE NOTED AS BEING |
| | WIRED INTO KIT/BATH LT CIRCUITS. |
| | |
| | 5)NOTE: PLEASE SEE MISSING REQUIRED |
| | RECEPT FOR BATH RM. TO BE W/IN 3' OF |
| | SINK. 210.52D/210.11C3 |
| | |
| | 6)NOTE: PLEASE SEE 210.52 FOR SOME |
| | RECEPTSMISSING. |
| | |
| | 7)NOTE: PLEASE CORRELATE LOADS SHOWN |
| | FOR AHU'S / AND LOAD CALCULATIONS ALONG |
| | WITH OCP. |
| | SHOWS 8KW AND 5KW ON ONE . |
| | LOADS IN LOAD CALCS? |
| | |
| | 8)NOTE: PLEASE SEE AN ELECTRICAL WATER |
| | HEATER IS SHOWN ON PANEL SCHEDULE AND |
| | LOAD CALCS, HOWEVER PLANS ARE SHOWING |
| | WH AS GAS?? |
| | |
| | 9)NOTE: PLEASE SEE 110.26 FOR MIN SPACE |
| | FOR A/C CU'S. #'S 1&2."REDLINE ITEM". |
| | |
| | 10)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 11)NOTE: PLEASE PROVIDE RM DESIGNATION |
| | ON PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |