| Plan Review Notes For Permit 04070064 |
| Permit Number |
04070064 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-11-21 00:00:00 | *** DENIED *** | | | 1) RETURN AIR DUCT TO BELOW NEEDS TO BE | | | 12", PER 2001 FBC/M 601.4 . | | | 2) RETURN AIR TO MASTER BEDROOM NEEDS TO | | | BE 14"X14" GRILL WITH 12" FLEX, PER 2001 | | | FBC/M 601.4 . | | | 3) RETURN AIR GRILL IN DINING ROOM | | | SHOULD BE 218 SQ. IN. OR LARGER. | | | 4) 8X16 TRUNK LINE FROM FIRST FLOOR DOES | | | NOT GO TO A.H.U. . | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|