Plan Review Notes
Plan Review Notes For Permit 04070064
Permit Number 04070064
Review Stop M
Sequence Number 5
Notes
Date Text
2005-11-21 00:00:00*** DENIED ***
 1) RETURN AIR DUCT TO BELOW NEEDS TO BE
 12", PER 2001 FBC/M 601.4 .
 2) RETURN AIR TO MASTER BEDROOM NEEDS TO
 BE 14"X14" GRILL WITH 12" FLEX, PER 2001
 FBC/M 601.4 .
 3) RETURN AIR GRILL IN DINING ROOM
 SHOULD BE 218 SQ. IN. OR LARGER.
 4) 8X16 TRUNK LINE FROM FIRST FLOOR DOES
 NOT GO TO A.H.U. .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.