2005-09-22 00:00:00*** DENIED ***
 1) A/C EQUIP. NOT SHOWING ON PLANS FOR
 ADDITION.
 2) NEED MOUNTING INFO. ON AM. STANDARD
 TCK-018. SHOS COMPLIANCE FOR THE 140 MPH
 WIND LOAD.
 3) AIR DUCT TRUNK LINE SIZES NOT
 SHOWING.
 4) SOME FLEX DUCT SIZES NOT SHOWING, AND
 CFM'S NOT SHOWING AT GRILLS.
 5) NO DRYER VENT SHOWING. SEE 2001 FBC/M
 504.6 .