| Plan Review Notes For Permit 04070064 |
| Permit Number |
04070064 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-22 00:00:00 | *** DENIED *** | | | 1) A/C EQUIP. NOT SHOWING ON PLANS FOR | | | ADDITION. | | | 2) NEED MOUNTING INFO. ON AM. STANDARD | | | TCK-018. SHOS COMPLIANCE FOR THE 140 MPH | | | WIND LOAD. | | | 3) AIR DUCT TRUNK LINE SIZES NOT | | | SHOWING. | | | 4) SOME FLEX DUCT SIZES NOT SHOWING, AND | | | CFM'S NOT SHOWING AT GRILLS. | | | 5) NO DRYER VENT SHOWING. SEE 2001 FBC/M | | | 504.6 . | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|