| Plan Review Notes For Permit 04070064 |
| Permit Number |
04070064 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | | | | 1) SHT M-2 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. | | | A) THE KITCHEN ISLAND SINK IS NOT VENT- | | | ED. SECTION 901.2.1 | | | B) THE 2ND FLOOR BATHROOMS SHALL NOT | | | DRAIN THRU THE VENT FOR THE 1ST FLOOR | | | KITCHEN SINK. A SEPARATE STACK IS REQ- | | | UIRED. SECTION 908.3 | | | C) SHOWER & TUB ARE NOT VENTED AS PIPED | | | CONNECT LINE TO SHOWER AND TUB TO VENTED | | | LINE DRAINING THE LAV'S. SECTION 901.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|