| Plan Review Notes For Permit 04070064 |
| Permit Number |
04070064 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-15 00:00:00 | DENIED: | | | PER 2001 FBC(M) 601.4, HABITABLE ROOMS | | | SEPARATED BY A DOOR SHALL HAVE RETURN | | | AIR.PLAN SHEET M-1, OFFICE AREA RETURN | | | AIR REQUIRED FROM THIS SPACE. | | | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | PLAN SHEET M-1, PLEASE CLARIFY MOUNTING | | | OF THE AMERICAN STANDARD TCK018.IS THE | | | LOCATION ON THE FLAT ROOF?PLEASE | | | PROVIDE DETAIL FOR MOUNTING, SHOW | | | COMPLIANCE FOR THE 140 MPH WIND LOAD. | | | HEIGHT REQUIREMENT FROM THE FINISHED | | | ROOF SHALL COMPLY WITH 2001 FBC 1511.7. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|