Plan Review Notes
Plan Review Notes For Permit 04070064
Permit Number 04070064
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-13 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 2} PLEASE SHOW GROUNDING PER 250.50,
 ALL AVAILABLE, AND THE GROUNDING
 ELECTRODE PER 250.66.
  
 3} THE LOAD CALCULATIONS ARE INCORRECT.
 PLEASE CALCULATE PER 220.31, OPTIONAL,
 OR 220.3 STANDARD.
  
 4} THE FOLLOWING ITEMS MUST BE
 CALCUTATED PER THE CORRESPONDING
 ARTICLES:
 A) RANGE -220.19 (8000VA)
 B) DRYER-220.18 (5000VA)
 C) LAUNDRY-220.16(B) (1500VA)
 D) SMALL APPLIANCE-220.16(A)-2 EACH AT
 1500VA.
 5} THE AHU'S MUST BE CALCULATED @ 100%
 PER 220.31.
  
 6} THE 65% OF THE REMAINDER OF THE LOAD
 IS INCORRECT PER 220.
  
 7} THE OCP IS TOO LARGE FOR THE
 CONDUCTORS FOR AHU #2. SEE 310.16.
  
 8} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 9} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3.
  
 10} ADDITIONAL RECEPTACLES ARE REQUIRED
 PER ARTICLE 210.52(A)(1) & (2) IN THE
 FOLLOWING ROOMS: BILLIARDS, KITCHEN,
 OFFICE, GUEST BEDROOM(UPSTAIRS).
 210.52(C) IN THE KITCHEN. 210.52(D)
 GUEST BATH, 210.52(E) AT THE REAR OF
 THE HOUSE.
  
 11} THE RECEPTACLES IN THE KITCHEN MUST
 COMPLY WITH 210.8(A)(6), GFI.
  
 12} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 13} THERE IS A PANEL SHOWN IN THE
 LAUNDRY ROOM IN VIOLATION OF 110.26.
 THIS PANEL IS NOT SHOWN ON THE RISER
 DIAGRAM, PLEASE SHOW SAME AND SUBMIT A
 PANEL SCHEDULE ON PLANS.
  
 IF THERE AR EANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026