| 2004-07-13 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT PER 110.9. |
| | |
| | 2} PLEASE SHOW GROUNDING PER 250.50, |
| | ALL AVAILABLE, AND THE GROUNDING |
| | ELECTRODE PER 250.66. |
| | |
| | 3} THE LOAD CALCULATIONS ARE INCORRECT. |
| | PLEASE CALCULATE PER 220.31, OPTIONAL, |
| | OR 220.3 STANDARD. |
| | |
| | 4} THE FOLLOWING ITEMS MUST BE |
| | CALCUTATED PER THE CORRESPONDING |
| | ARTICLES: |
| | A) RANGE -220.19 (8000VA) |
| | B) DRYER-220.18 (5000VA) |
| | C) LAUNDRY-220.16(B) (1500VA) |
| | D) SMALL APPLIANCE-220.16(A)-2 EACH AT |
| | 1500VA. |
| | 5} THE AHU'S MUST BE CALCULATED @ 100% |
| | PER 220.31. |
| | |
| | 6} THE 65% OF THE REMAINDER OF THE LOAD |
| | IS INCORRECT PER 220. |
| | |
| | 7} THE OCP IS TOO LARGE FOR THE |
| | CONDUCTORS FOR AHU #2. SEE 310.16. |
| | |
| | 8} PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 9} PLEASE LIST ALL THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3. |
| | |
| | 10} ADDITIONAL RECEPTACLES ARE REQUIRED |
| | PER ARTICLE 210.52(A)(1) & (2) IN THE |
| | FOLLOWING ROOMS: BILLIARDS, KITCHEN, |
| | OFFICE, GUEST BEDROOM(UPSTAIRS). |
| | 210.52(C) IN THE KITCHEN. 210.52(D) |
| | GUEST BATH, 210.52(E) AT THE REAR OF |
| | THE HOUSE. |
| | |
| | 11} THE RECEPTACLES IN THE KITCHEN MUST |
| | COMPLY WITH 210.8(A)(6), GFI. |
| | |
| | 12} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 13} THERE IS A PANEL SHOWN IN THE |
| | LAUNDRY ROOM IN VIOLATION OF 110.26. |
| | THIS PANEL IS NOT SHOWN ON THE RISER |
| | DIAGRAM, PLEASE SHOW SAME AND SUBMIT A |
| | PANEL SCHEDULE ON PLANS. |
| | |
| | IF THERE AR EANY QUESTIONS PLEASE CALL. |
| | |