| Plan Review Notes For Permit 04070034 |
| Permit Number |
04070034 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-09-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | 1) REVISION NOT CLEAR AND HARD TO READ. | | | 2) SIGNATURE AND PRINTED NAME OF PERSON | | | THAT DESIGNED THE PLAN ORIGINALLY SHALL | | | NEED TO BE RESIGNED IF DESIGNED BY THAT | | | PERSON. IF NOT NEW NAME TO BE PRINTED | | | ON PLAN AND NEW SIGNATURE REQUIRED, | | | 3) INDICATE SIZE OF EXISTING PE PIPE TO | | | EXISTING GRILL LINE. | | | 4) GAS PRESSURE NOTED AS 8" WC, PLEASE | | | CLARIFY AS ALL FBC-2001 CHARTS ARE FOR | | | 1/2 LB OR 12" TO 14" WC. | | | 5) INDICATE WHY THE 6" SLEEVE IS BEING | | | USED. WHAT IS ABOVE THE SLEEVE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|