Plan Review Notes
Plan Review Notes For Permit 04070034
Permit Number 04070034
Review Stop P
Sequence Number 2
Notes
Date Text
2004-09-21 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) REVISION NOT CLEAR AND HARD TO READ.
 2) SIGNATURE AND PRINTED NAME OF PERSON
 THAT DESIGNED THE PLAN ORIGINALLY SHALL
 NEED TO BE RESIGNED IF DESIGNED BY THAT
 PERSON. IF NOT NEW NAME TO BE PRINTED
 ON PLAN AND NEW SIGNATURE REQUIRED,
 3) INDICATE SIZE OF EXISTING PE PIPE TO
 EXISTING GRILL LINE.
 4) GAS PRESSURE NOTED AS 8" WC, PLEASE
 CLARIFY AS ALL FBC-2001 CHARTS ARE FOR
 1/2 LB OR 12" TO 14" WC.
 5) INDICATE WHY THE 6" SLEEVE IS BEING
 USED. WHAT IS ABOVE THE SLEEVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]