Plan Review Notes
Plan Review Notes For Permit 04061379
Permit Number 04061379
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-10 00:00:00DENIED;
 1.LINE DRAWING ON P.A-2 SHOWS 3" TO 2ND
 FLOOR PLUMBING, RISER DIAGRAM (A-3)
 SHOWS 4" PLEASE CORRECT.
 2.BATH #3 W/C IS NOT VENTED. MAX. OF 12
 FIXTURE UNITS PERMITED PER TABLE
 909.3.
 3.PLEASE CHANGE TEST TEE TO 2 WAY C.O.
 4. MASTER BATH LAVS. ARE TOO FAR APART
 FOR ONE VENT.
 5.SEE RED LINES ON RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 8056695