| Plan Review Notes For Permit 04061379 |
| Permit Number |
04061379 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-10 00:00:00 | DENIED; | | | 1.LINE DRAWING ON P.A-2 SHOWS 3" TO 2ND | | | FLOOR PLUMBING, RISER DIAGRAM (A-3) | | | SHOWS 4" PLEASE CORRECT. | | | 2.BATH #3 W/C IS NOT VENTED. MAX. OF 12 | | | FIXTURE UNITS PERMITED PER TABLE | | | 909.3. | | | 3.PLEASE CHANGE TEST TEE TO 2 WAY C.O. | | | 4. MASTER BATH LAVS. ARE TOO FAR APART | | | FOR ONE VENT. | | | 5.SEE RED LINES ON RISER DIAGRAM. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 8056695 |
|