Plan Review Notes
Plan Review Notes For Permit 04061379
Permit Number 04061379
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-07 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE SYSTEM MUST
 COMPLY WITH ALL THAT ARE AVAILABLE TO
 BE BONDED TOGETHER.CWP & FOOTER STEEL.
 PLEASE NOTE THE ARTICLE REFERRED TO
 (250-83) IS OUT OF THE 1996 CODE, SEE
 2002.
  
 2} THE RISER DIAGRAM SHOWS # 12 FEEDING
 THE POOL PANEL AND THE PANEL SCHEDULE
 INDICATES #8'S. PLEASE CORRELATE. ALSO
 NOTE BREAKER SIZE.
  
 3} THE PANEL SCHEDULE HAS A SMALL
 APPLIANCE AND THE POOL PUMP CIRCUITS ON
 A 30 AMP BREAKER WITH #12 WIRE. SEE
 310.16.
  
 4} THE RISER SHOWS A DISCONNECT ON THE
 SERVICE AND IT DOES NOT APPEAR ON THE
 DRAWING, PLEASE INDICATE LOCATION.
  
 5} THE DISCONNECTS SHOWN BEHIND THE
 CONDENSING UNITS DO NOT COMPLY WITH
 110.26.
  
 6} A SMOKE DETECTOR IS REQUIRED AT THE
 STAIRWELL,1ST FL,TO COMPLY WITH 905.2.2
 FBC.
  
 7} BATH #3 MUST HAVE ANOTHER RECEPTACLE
 AT THE 2ND SINK TO COMPLY WITH 210.52(D)
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026