| Plan Review Notes For Permit 04061379 |
| Permit Number |
04061379 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-07 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE GROUNDING ELECTRODE SYSTEM MUST | | | COMPLY WITH ALL THAT ARE AVAILABLE TO | | | BE BONDED TOGETHER.CWP & FOOTER STEEL. | | | PLEASE NOTE THE ARTICLE REFERRED TO | | | (250-83) IS OUT OF THE 1996 CODE, SEE | | | 2002. | | | | | | 2} THE RISER DIAGRAM SHOWS # 12 FEEDING | | | THE POOL PANEL AND THE PANEL SCHEDULE | | | INDICATES #8'S. PLEASE CORRELATE. ALSO | | | NOTE BREAKER SIZE. | | | | | | 3} THE PANEL SCHEDULE HAS A SMALL | | | APPLIANCE AND THE POOL PUMP CIRCUITS ON | | | A 30 AMP BREAKER WITH #12 WIRE. SEE | | | 310.16. | | | | | | 4} THE RISER SHOWS A DISCONNECT ON THE | | | SERVICE AND IT DOES NOT APPEAR ON THE | | | DRAWING, PLEASE INDICATE LOCATION. | | | | | | 5} THE DISCONNECTS SHOWN BEHIND THE | | | CONDENSING UNITS DO NOT COMPLY WITH | | | 110.26. | | | | | | 6} A SMOKE DETECTOR IS REQUIRED AT THE | | | STAIRWELL,1ST FL,TO COMPLY WITH 905.2.2 | | | FBC. | | | | | | 7} BATH #3 MUST HAVE ANOTHER RECEPTACLE | | | AT THE 2ND SINK TO COMPLY WITH 210.52(D) | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|