| Date |
Text |
| 2005-10-08 00:00:00 | ********* UNSAT *********** |
| | |
| | |
| | 1)NOTE: PLEASE SEE PLANS ARE NOW COMING |
| | IN WITH ALL NEW LOW VOLTAGE SYSTEMS |
| | WHICH HAVE NOT BEEN PERMITTED. |
| | PLEASE SUBMIT COMPLETE PLANS AND PERMIT |
| | APPLICATION FOR ALL LV SYSTEMS WITH THE |
| | EXCEPTION OF TELEPHONE, CATV AND ALARM. |
| | PLEASE SEE HOME AUDOMATION SYSTEM MAY BE |
| | REVISED AND INLCUDED WITH MAIN |
| | ELECTRICAL CONTRACTOR AS LONG AS THE |
| | CONTRACTOR IS TAKING FULL RESPONSIBILTY |
| | FOR SUCH WORK. PLEASE ALSO KNOW, IF |
| | EXISTING ELECTRICAL CONTRACTOR IS TAKING |
| | THE RESPONSIBILITY, REVISED PLANS WOULD |
| | ALSO INLCLUDE A VALUATION ADJUSTMENT TO |
| | INCLUDE ALL NEW SYSTEMS. LABOR AND |
| | MATERIALS. |
| | PLEASE PROVIDE SIGNED CONTRACTS FOR |
| | SCOPE OF WORK.104.6.5 FBC CITY WIDE |
| | ADMINISTRATIVE CODE. |
| | ALL LV IS NOT INCLUDED IN ELECTRICAL |
| | CONTRACTORS PERMIT. |
| | |
| | 2)NOTE: PLEASE SEE RISER DIAGRAM HAS |
| | BEEN COMPLETELY REVISED TO INCLUDED ATS |
| | SWITCHES, NEW PANELS ETC. |
| | PLEASE SEE THIS WILL ALSO BE REQUIRED TO |
| | UPDATE VALUE. |
| | |
| | 3)NOTE:PLEASE SEE NEW PANEL "E" WHICH |
| | INDICATES A NEW GAZEBO, HOWEVER THIS |
| | "GAZEBO" IS NOT ON PLANS. |
| | PLEASE SEE THAT BLDG MAY REQUIRE GAZEBO |
| | TO BE UNDER A SEPARATE PERMIT. IF NOT, |
| | PLEASE SUBMIT REVISE BLDG PLANS, SURVEY |
| | FOR ZONING ETC. |
| | IF GAZEBO IS A DETACHED BLDG, PLEASE SEE |
| | THAT PANEL "E" WILL BE REQUIRD TO HAVE A |
| | MCB. 225.31 |
| | PLEASE ALSO SEE LOACTION WILL HAVE TO BE |
| | DETERMINED FOR CODE COMPLIANCE ONCE |
| | PLANS ARE SUBMITTED. |
| | PLEASE INCLUDE NEW GROUNDING ELECTRODE |
| | SYSTEM AT DETACHED BLDG.250.32 |
| | FOOTER STEEL, CWP ETC. |
| | 250.50 |
| | |
| | 4)NOTE: PLEASE SUBMIT MORE INFORMATION |
| | FOR HOME AUTOMATION PANELS. PANEL"C" |
| | INDICATES 60A,50 ETC OCP FEEDING ????? |
| | 240.4,310.16, 215.5 |
| | |
| | 5)NOTE: PLEASE SUBMIT COMPLETE |
| | MANUFACTURE SPECS FOR ATS'S. |
| | NOT INCLUDED UNDER THIS PERMIT. |
| | |
| | 6)NOTE: PLEASE SEE 210.52 WHICH REQUIRES |
| | RECEPT SPCING TO MEET CODE ALONG RAIL |
| | ARE IN BILLIARD /LOUNGE. RAILIS |
| | CONSIDERED WALL SPACE. |
| | |
| | 7)NOTE: PLEASE VERIFY TAPPED CONDUCTORS |
| | IN GUTTER TO ATS'S SW CAN NOT BE |
| | VERIFIED AS APPLICATION FOR GENERATOR |
| | HAS BEEN SUBMITTED. |
| | |
| | 8)NOTE: PLEASE SEE 110.26 FOR MIN |
| | CLEARNECE REQUIRED FOR POOL PANEL. |
| | |
| | PLEASE SUBMIT ALL PERMIT APPLICATIONS |
| | FOR SCOPE OF REQUIRED TO BE UNDER |
| | SEPARATE PERMITS. |
| | PLEASE CORRECT PLANS FOR ABOVE COMMENTS. |
| | PLEASE SUBMIT ADJUST VALUES. |
| | PLEASE RE-SUBMIT THESE PLANS AFTER THIS |
| | IS DONE. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO |
| | NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2005-10-07 00:00:00 | IN ELEC FOR REVIEW. |