| 2004-07-07 00:00:00 | *************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SEE 210.63 FOR MISSING |
| | RECEPT FOR A/C UNITS. |
| | |
| | 2)NOTE: PLEASE VERIFY OCP FOR 7.5KW |
| | AHU'S. SHOWN WITH 60A |
| | |
| | 3)NOTE: PLEASE CORRELATE PANEL "C" OCP |
| | AND RATING. RISER SHOWS AS 50A AND |
| | PANEL "B" SCHEDULE SHOWS 60A? |
| | |
| | 4)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | PLACEMENT. AREAS MARKED ON ONE SET OF |
| | PLANS. PLEASE ALSO SEE RAIL AREAS ARE |
| | ALSO CONSIDERED AS WALL SPACE. |
| | |
| | 5)NOTE: PLEASE SEE 210.52D , RECEPTS TO |
| | BE W/IN 3' OF SINKS. |
| | |
| | 6)NOTE: SD TO BE MOVED INTO MASTER BEDRM |
| | NFPA-72 8-1.4.1.6.2 |
| | |
| | 7 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 8 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 9)NOTE: PLEASE SEE PLANS INDICATE A |
| | MAIN DISCONNECT OUTSIDE, YET RISER DOES |
| | NOT SHOW THIS? PLEASE VERIFY THIS? |
| | |
| | 10)NOTE: PLEASE SEE 220.14, 430.24,25,26 |
| | FOR LOAD CALCULATION TO FIGURED FOR |
| | PANEL "C". |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |