| 2005-12-07 00:00:00 | ********* UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE FOUNTAIN PUMP SHOWN |
| | WITH 20A OCP ON #14. |
| | |
| | 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE |
| | FOR POOL PANEL AND PANEL "B"&"A"WITH |
| | RISER DIAGRAM. |
| | RISER SHOWS PANEL "B" FEEDING POOL |
| | PANEL, HOWEVER PANEL "A" SCHEDULE |
| | INDICATES POOL PANEL COMING FROM THIS |
| | LOCATION. |
| | PLEASE SEE PANEL "A" SHOWS 60A OCP AND |
| | #6 TO POOL PANEL. POOL PANEL ON RISER IS |
| | SHOWN AS 60A OCP AND #4. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE SD IN MASTER BEDRM |
| | AND OTHER LOCATIONS ARE ALL REQUIRED TO |
| | BE WITHIN 12"OF THE HIGHEST |
| | POINT OF A FLAT CEILING, AND WITHIN 3' |
| | OF THE PEAK ON A SLOPED CEILING. |
| | PLEASE KNOW, IF TRAY CEILING IS 12" OR |
| | MORE ABOVE OTHER CEILING IN RM, THE SD |
| | WILL BE REQUIRED TO BE LOCATED IN TRAY |
| | CEILING AREA. |
| | NFPA-72 11.8.3.5 |
| | |
| | 4)NOTE: PLEASE CORRELATE THE NUMBER OF |
| | RECESSED LTS ON PLANS WITH THE # IN LOAD |
| | CALCS ETC. |
| | PLEASE SEE LOAD CALCS INDICATE A TOTAL |
| | OF 90, HOWEVER THERE ARE MORE ON PLANS |
| | PLEASE ADJUST. |
| | 220.3B4 |
| | |
| | 5)NOTE: PLEASE SEE AHU#2 ON PANEL |
| | SCHEDULE WHICH INDICATES A 10KW HEAT, |
| | YET OCP IS SHOWN AT 50A'S. PLEASE SEE |
| | 424.3 WHICH REUIRES A MIN 125%. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |