| 2005-10-21 00:00:00 | ******* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE CORRELATE ALL A/C |
| | MECHANICAL EQUIPMENT. |
| | PLEASE SEE PANEL SCHEDULES INDICATE FOUR |
| | A/C SYSTEMS, HOWEVER PLANS DO NOT SHOW |
| | FOUR COMPLETE SYSTEMS. |
| | PLEASE ALSO SEE A/C #3 IS NOTED FOR |
| | GARAGE, HOWEVER THIS SYSTEM IS SHOWN |
| | NEXT TO MASTER BR. |
| | PLEASE SEE OTHERS. |
| | PLEASE SEE LOADS FOR EACH PANEL THE |
| | LARGETS LOADS FOR A/C SYSTEMS ARE TO BE |
| | FIGURED USUALLY THE HEAT LOAD. IF ONLY |
| | THE COOLING LOAD IS INDICATED ON ONE |
| | PANEL, THEN COOLING LOAD MUST BE SHOWN. |
| | 220 |
| | |
| | 2)NOTE: PLEASE SEE BOTH PANELS "A" AND |
| | "B" INDICATE BEING MLO. |
| | PLEASE SEE RISER SHOWS THESE AS MCB. |
| | PLEASE CORRELATE AND INDICATE MCB'S AS |
| | REQIRED 230.70 |
| | |
| | 3)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | IS NOW SHOWN GOING TO SLAB, HOWEVER THIS |
| | SHOULD BE NOTED AS FOOTER STEEL. 250.50 |
| | |
| | 4)NOTE: PLEASE SEE LARGEST MOTOR LOADS |
| | AND CONTINUOUS LOADS IN POOL PANEL NEED |
| | TO BE SHOWN AT 125%. |
| | 215.3,230.42 |
| | |
| | |
| | |
| | ** NOTE ALL SD'S ARE TO BE INSTALLED |
| | WITH IN THE HIGHEST POINT OF A FLAT |
| | CEILING. |
| | PLEASE SEE THAT ALL SD'S ARE TO BE |
| | INSTALLED WITHIN 3' OF A SLOPED CEILING |
| | PEAK. |
| | PLEASE SEE MASTER BEDRM. |
| | PLEASE SEE BEDRM #4. |
| | PLEASE BE SURE TO VERIFY INSTALLATION IN |
| | FIELD. |
| | NFPA-72 8-1 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |