| Plan Review Notes For Permit 04061350 |
| Permit Number |
04061350 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-06 00:00:00 | ************* UNSAT ************* | | | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | AND PANELS. RISER SHOWS PANELS AS 150A'S | | | AND FED W/ 200A BRKRS. PANEL SCHEDULE | | | INDICATES 200A PANELS. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE 250.66 FOR SIZING | | | OF GROUNDING ELECTRODE CONDUCTOR. | | | 400A SERVICE INDICATED. | | | | | | 3)NOTE: PLEASE SEE OCP SHOWN FOR 7.5KW | | | HEAT ON AHU #3, | | | | | | 4)NOTE: PLEASE SEE PLANS DO NOT SHOW | | | GFI RECEPT FOR WHIRLPOOL TUB AS SHOWN | | | ON PANEL SCHEDULE. | | | | | | 5)NOTE: PLEASE SEE 210.52C1-5 FOR RECEPT | | | REQUIRED ALONG COUNTERSPACE. ? | | | | | | 6)NOTE: PLEASE SEE 210.52 FOR RECEPT IN | | | BEDRM #2 | | | | | | 7) NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210.8A-6 | | | | | | 8)NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|