| 2004-07-13 00:00:00 | BUILDING PLAN REVIEW: FAILED | | | | | | 1. PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT. THE COPY MUST BE SUBMITTED | | | BEFORE A PERMIT IS ISSUED. | | | | | | 2. SUBMIT ENGINEERING FOR THE BUTT GLASS | | | ASSEMBLY WITH PRODUCT APPROVALS.THE | | | ENGINEER MUST INSPECT THE WINDOWS AT | | | TIME OF INSTALLATION AND SUBMIT A | | | LETTER STATING THEY HAVE BEEN INSTALLED | | | ACCORDING TO HIS CALCULATIONS. | | | SUBMIT THE PROPER PRODUCT APPROVALS FOR | | | THE WINDOWS. SUBMIT THE MFGRS. PRODUCT | | | SHEET FOR THE SEALANT TO BE USED IN THE | | | INSTALLATION. | | | | | | 3. SUBMIT PRODUCT APPROVAL AND | | | INSTALLATION SCHEDULE FOR THE STORM | | | PANELS. | | | | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|