Plan Review Notes
Plan Review Notes For Permit 04061323
Permit Number 04061323
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-02 00:00:00****** UNSAT *********
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL SCHED-
 -ULE TO BE SUBMITTED.
 PLEASE ALSO SHOW ALL MIN REQUIRED CIR-
 -CUITS FOR NEW WORK. PER 2002 NEC
  
 2)NOTE: PLEASE SEE 2002 NEC FOR REQUIRED
 ARC FAULT PER 210.12
  
 3)NOTE: PLEASE SEE PANEL MAY NOT BE IN
 BATH ROOM. APPEARS TO BE SHOWN IN
 MASTER BATH??240.24E
  
 PLEASE SEE NOTES FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  