| 2005-05-05 00:00:00 | REVISION DATED 3/30/05 |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.) SHEET A1.1 SHOWS THE FREIGHT LIFT AS |
| | REMAINING, S1 SHOWS THE LIFT REMOVED. |
| | STRUCTURALS AND ARCHITECTURALS SHOULD BE |
| | CONSISTENT. |
| | |
| | 2.)PROVIDE STAIR WIDTHS, FBC1004. |
| | |
| | 3.)DECLARE AN OCCUPANT LOAD, FBC TABLE |
| | 1003.1. |
| | |
| | 4.)THE PRODUCT APPROVAL FOR THE |
| | EXTERIOR DOOR AND THE ENERGY CALC HAVE |
| | BEEN STAMPED AND A COPY RETAINED. |
| | |
| | 5.)SEE PREVIOUS LIST IN REGARDS TO |
| | VERTICAL ACCESSIBILITY, FBC11-4.1.3. |
| | HOW IS THIS BEING ADDRESSED? |
| | |
| | 6.)A 1 HR PROTECTED STAIR IS SHOWN |
| | A1.0.PLEASE EXPLAIN HOW 1 HR IS |
| | MAINTAINED THROUGH THE SECOND FLOOR. |
| | SEE FBC1006.1.3.1, 705.1.2.OPENINGS |
| | ARE SHOWN WITHOUT FIRE RESISTANCE |
| | INFORMATION. |
| | |
| | 7.)A1.2, STAIR DETAILS HAS TWO DETAILS |
| | WHICH ARE ILLEGIBLE. |
| | |
| | 8.)A HANDRAIL IN COMPLIANCE WITH |
| | FBC1007.5 IS REQUIRED ON BOTH SIDES OF |
| | THE STAIRS FBC1007.5.2.ONLY ONE IS |
| | SHOWN. |
| | |
| | 9.)SHEET A1.2, AN EXIT CORRIDOR IS |
| | SHOWN.WHERE IS THIS ON THE PLAN?IT |
| | REFERS TO UL-U465; PROVIDE THIS DETAIL |
| | ON THE PLAN. |
| | |
| | 10.) WHEN RESUBMITTING, PLEASE PROVIDE A |
| | TRANSMITTAL SHEET EXPLAINING HOW THESE |
| | ITEMS ARE BEING ADDRESSED. |
| | |
| | 11.)NOTE - STRUCTURALS SUBMITTED |
| | SEPARATELY REVIEWED AGAIN AND PUT WITH |
| | ARCHITECTURAL REVISION. |