| 2005-04-05 00:00:00 | ********* UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS |
| | REVIEW AND REVIEW ON 11/29/04 |
| | |
| | 2)NOTE: PLEASE SEE AS REQUESTED ON |
| | PREVIOUS REVIEW: LETTERS FROM BOTH THE |
| | ORIGINAL ARCHITECT AND ENGINEER WERE |
| | REQUESTED TO RELEASE THEM FROM DESIGNERS |
| | OF RECORD. THIS REQUEST WAS TO EACH HAVE |
| | SIGNED, DATED, SEALED AND NOTORIZED |
| | LETTERS. |
| | PLEASE SEE ENGINEER'S LETTER WAS NOT |
| | NOTORIZED AND ARCH'S LETTER WAS NOT |
| | SEALED, DATED OR NOTORIZED. |
| | |
| | 3)NOTE: PLEASE SEE THE FOLLOWING EXCERPT |
| | TAKEN DIRECTLY FROM NOTES ON 11/29/04 |
| | FOR REDLINED PLANS. |
| | |
| | ***** PLANS REDLINED ****** |
| | |
| | 1)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | CONDUCTOR STILL NOT SHOWN PER 250.66. |
| | TWO SETS OF 3/0'S,,,, 1/0 MIN GEC. |
| | |
| | |
| | 2)NOTE: PLEASE ALSO SEE AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS NOW ADDED FROM |
| | METER TO MAIN? AN EQUIPMENT GRND IS NOT |
| | INSTALLED UNTIL AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | 250.6, 250.24 |
| | |
| | |
| | ** BOTH OF THE ABOVE WERE REDLINED ON |
| | PLANS. IF ANY REV'S ARE MADE TO PLANS, |
| | PLEASE ALSO CORRECT THE ABOVE AT THAT |
| | TIME. *** |
| | |
| | 4)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EM/EXT LTS. THIS WAS NOTED |
| | ON ALL PREVIOUS REVIEWS AND SOME |
| | CIRCUITING IS STILL NOT SHOWN AND SOME |
| | NOT PER 700.12E. |
| | |
| | PLEASE SEE FS 553.80(2)(B) WITH RESPECT |
| | TO DESIGN PROFESSIONAL. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | |
| | PLEASE MAKE THE ABOVE CORRECTIONS AND |
| | SUBMIT REVISED PLANS FOR REVIEW. ONCE |
| | AGAIN, IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL TO GO |
| | OVER ANY COMMENTS. |
| | THIS WAS STATED ON ALL 5 PREVIOUS |
| | REVIEWS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |